|
|
|
Parent Menu
Same Level Menu
Child Menu
Questions/Comments
|
Transmission Operations - System-wide Automatic Voltage Control FunctionContentsNarrativePerform wide-area voltage control through closed loop control by measuring the wide area voltages, computing a control solution, and effecting wide area control System wide voltage and subsequent power flow can be optimized by looking at the voltage profile for a large segment of the power grid, choosing set-points for the voltages at the various control points, and issuing the appropriate control commands to effect the desired operating point. Prior to starting the voltage control process, the system would need to determine the availability (in/out of service) and capacity of all the control points around the system. This information would then have to be factored into the voltage control algorithm. For example, if part of a series capacitor bank is out of service, the remaining available series impedance shall be reported; if an SVC is out of service, this shall be reported to the Controller. Voltage (phase and sequence) from 10 to a few hundred points around the power system are to be measured and transmitted to one or more Controllers located around the power system. Each Controller analyzes the measured voltages and computes an optimal voltage control solution. The control solution would include linear control of generator voltage and synchronous condenser outputs, transformer tap changer control, voltage regulator control, Thyristor controlled Series Capacitor (TCSC) control, Static Var Capacitor control, DC link power flows, as well as on/off control of series and shunt capacitor banks and reactor switching. A measure/control link to DER/ADA/Consumer/Industrial devices is also envisioned that would enable some voltage support/load shed (in emergency conditions) from the distribution system. Upon issuance of the control command, the device receiving the command shall acknowledge that the voltage control command was received and subsequently executed. This devices in this scenario would also be used for Voltage Security (see Voltage Security use case) and the steps for Voltage Security are called out as an alternate sequence in the function steps. On failure of the communication system to a particular node, that node shall resort to local voltage control with previously calculated set-points. Failure of communication to any remote node shall be immediately (within 1 second) to the system operator and other monitoring points as desirable. StepsNormal Sequence Steps
Steps – Alternative / Exception Sequences
|
|
IntelliGrid Architecture
|