Transmission Automated Control - Emergency Control Baseline FunctionContentsNarrativeThe purpose of the Wide Area Monitoring and Control Systems - Emergency Operations function is to provide communications services permitting an operator to take the following actions in response to a fault in the power system:
A complete narrative of the Function from a Domain Expert’s point of view, describing what occurs when, why, how, and under what conditions. This will be a separate document, but will act as the basis for identifying the Steps in Section 2. Emergency operations are organizational sequences of activities that involve multiple integrated actors exchanging information when a fault is detected on a power system. These activities are integrated through the use of Wide Area Control and Monitoring Systems (WAMACS) that provide operational control over the distributed network of actors that comprise the SCADA system. Each utility maintains their own WAMACS but in the future these systems must be linked to provide overall control and monitoring across multiple organizations to meet the future demands of the suppliers and users of electrical power. The remainder of this narrative describes an example scenario illustrating the characteristics and sequence of activities that occur on the power system during Emergency Operations. The example is based on a typical substation with a SCADA system.
|
|
# |
Event |
Name of Process/Activity |
Description of |
Information Producer |
Information |
Name of Info Exchanged |
Additional Notes |
IntelliGrid Architecture Environments |
|
1.1 1 |
Fault |
Report Fault |
Detects fault and trips appropriate breaker. |
Protective Relay |
Data Concentrator (sometimes GUI) |
Fault Indication
|
Must be detected within a cycle. Timestamp requires accurate synchronization |
|
|
1.2 |
|
Generate Report |
Send indication that a fault record is available. |
Fault Recorder Device |
Data Concentrator or GUI |
Fault Indication |
|
|
|
1.3 |
|
Report COS |
Identifies data as being of interest to the GUI. Translates protocol from IED to GUI. |
Data Concentrator |
GUI |
Fault Indication |
Concentrator required due to slow links, large numbers of devices. Legacy protocols may not support timestamp. May sort events by timestamp before transmission May distribute to multiple GUIs. |
|
|
1.4 |
|
Notification of Alarm |
Identifies the trip as an alarm condition and displays notification on screen. Maps point number and state to human-readable information. Logs the alarm / change of state. |
GUI |
System Operator |
Notification of Alarm |
Location, priority, description must all be pre-configured. |
|
|
2.1 |
Retrieve Fault |
Retrieve Fault |
Retrieves the fault record from the fault recorder. |
IED |
Data Concentrator or GUI |
Analog and digital sample file |
Large volumes of data. Many data concentrators cannot forward files. Legacy protocols may not support file transfer. Existing links may make transfer slow. Sometimes may need to send operator to site. |
|
|
3.1 |
Change in line load |
Change in line load |
Detect change in load due to protection activity. |
IEDs |
Data Concentrator or GUI |
Change in Line Load
|
|
|
|
3.2 |
|
Change in Analog Data |
Identifies data as being of interest to the GUI. Identifies the change as being significant (deadband). Converts communications protocol from IED to GUI. |
Data Concentrator |
GUI |
Change in Line Load |
May distribute to multiple GUIs. |
|
|
3.3 |
|
Load Change |
Maps point number to database. Updates values if currently on display. Raises alarm if threshold exceeded. Logs data if it is being trended. |
GUI |
System Operator |
Voltage, Current |
Scaling is usually pre-configured |
|
|
4.1 |
Shed Load, or Restore Power |
Shed Load / Restore Power |
Operates control |
System Operator |
GUI |
|
|
|
|
4.2 |
|
Send Control |
Sends control or setpoint |
GUI |
Data Concentrator or IED |
Send Control |
Normally uses Select-Before-Operate service. Occasionally broadcast. |
|
|
4.3 |
|
Forward Control |
Translates control or setpoint and sends to IED. |
Data Concentrator |
IED |
Send Control |
Uses Select-Before-Operate service. Often supports multiple GUIs. |
|
|
5.1 |
Locate Fault |
Locate Fault |
Measures impedance of line and calculates distance based on pre-configured characteristics of the line. |
Protective Relay |
Data Concentrator or GUI |
Locate Fault |
|
|
|
5.2 |
|
Display Location |
Displays location and distance on GUI in a manner that shows overlap. Logs distance and direction. |
GUI |
System Operator |
Display Location |
|
|
|
6.1 |
Dispatch |
Dispatch Field Personnel |
Dispatches crew based on fault location log and display. |
System Operator |
Field Personnel |
Directions |
Currently does not use SCADA network |
User Interface |
|
7.1 |
Notify |
Notify Personnel |
Notifies personnel that a service-affecting fault has occurred based on an alarm condition. |
GUI, Data Concentrator , System Operator |
Protection Engineer, Management Personnel |
Request to contact operator |
May or may not be automated. Typically does not use SCADA network |
User Interface |
|