|
|
|
Parent Menu Same Level Menu
Child Menu
Questions/Comments
|
IntelliGrid Architecture EnvironmentsAn IntelliGrid Architecture Environment is defined as a communication/information environment where the configuration, quality of service, security, and data management requirements of functions are the same or very similar | ||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
|
No. |
Name |
Security |
QoS |
Config |
Data Mgmt |
Sub |
CC |
Field |
Cust |
Bus |
|
1 |
Deterministic Rapid Response Intra-Sub |
H |
H |
|
Y |
|
|
|
|
|
|
2 |
Deterministic Rapid Response Inter-Site |
M |
H |
H |
H |
Y |
Y |
Y |
|
|
|
3 |
Critical Operations Intra-Substation |
H |
M |
H |
|
Y |
|
|
|
|
|
4 |
Inter-Field Equipment |
|
|
M |
|
|
|
Y |
|
|
|
5 |
Critical Operations DAC |
H |
M |
H |
H |
Y |
Y |
Y |
|
|
|
6 |
Non-Critical Operations DAC |
|
M |
|
|
Y |
Y |
Y |
|
|
|
7 |
Intra-CC |
|
M |
|
H |
|
Y |
|
|
|
|
8 |
Inter-CC |
H |
|
M |
H |
|
Y |
|
|
|
|
9 |
CC to ESP |
H |
|
M |
H |
|
Y |
|
|
Y |
|
10 |
RTO to Market Participant |
H |
|
M |
H |
|
|
|
|
Y |
|
11 |
CC to Customer Equipment |
M |
M |
H |
H |
|
Y |
|
Y |
|
|
12 |
CC to External Corporations |
H |
|
|
H |
|
Y |
|
|
Y |
|
13 |
Intra-Corporation |
M |
|
H |
H |
|
Y |
|
|
Y |
|
14 |
Inter-Corporation |
H |
|
M |
H |
|
|
|
|
Y |
|
15 |
DER Monitoring and Control |
H |
M |
H |
H |
|
Y |
|
Y |
|
|
16 |
Intra-Customer Site |
M |
H |
|
|
|
|
|
Y |
|
|
17 |
Inter-Customer Site |
H |
|
H |
|
|
|
Y |
Y |
|
|
18 |
Customer to ESP |
H |
|
H |
|
|
|
|
Y |
Y |
|
19 |
HV Generation Plant |
H |
M |
H |
|
Y |
|
|
|
|
|
20 |
Field Equipment and Maintenance |
M |
|
H |
H |
Y |
|
Y |
Y |
|
Table Summary of IntelliGrid Architecture Environment Requirements
General ratings for Security, Quality of Service (QoS), Configuration (Config) and Data Management (Data Mgmt)
H = high level of requirements; M= medium level of requirements; blank = low level of requirements
Indications of physical locations: Substation (Sub), Control Center (CC), Field Devices (Field), Customer site (Cust), Business (Bus)
Y= Yes, involves communication with that physical location.
· 1. Deterministic Intra-Substation: High speed intra-substation environment (e.g. protective relaying, direct monitoring of power system parameters by CTs and PTs)
· 2. Deterministic Inter-Site: High speed inter-site (e.g. distance protective relaying, FSM)
· 3. Critical Operations Intra-Substation: High security intra-substation environment (e.g. monitoring and control of IEDs, setting protective relay and other substation equipment parameters, …)
· 4. Inter-Field Equipment: Inter-field devices environment (e.g. monitoring and control of IEDs on feeders, …)
· 5. Critical Operations DAC: High security between control center and field equipment environment (e.g. monitoring and control by SCADA of substation and DA equipment, monitoring and control of DER devices, monitoring of security-sensitive customer meters, monitoring and control of generation units)
· 6. Non-Critical Operations DAC: Lower security interactions among control center, substation, field equipment, customer sites environment (e.g. monitoring non-power system equipment, less security-sensitive substations, customer site PQ monitoring, customer metering)
· 7. Intra-Control Center: Within one control center (e.g. SCADA system, EMS system, ADA functions, real-time operations)
· 8. Inter-Control Center: Among control centers (e.g. between utility control centers, between RTOs, between remote subsidiary or supervisory centers)
· 9. Control Centers to ESPs: Between utility control centers and ESPs/Aggregators (e.g. RTP, metering and settlements, market operations)
· 10. RTOs to Market Participants: Between utility/RTO/ISO control centers and Market Participants (e.g. market operations)
· 11. Control Center to Customers: Between customer equipment and utility control centers (e.g. customer metering, demand response interactions, DER management)
· 12. Control Center to Corporations: Between control centers and external corporations (e.g. weather data, regulators, auditors, vendors)